Altitude: | Up To 3, 000m Above Sea Level | Rated Voltage Of Main Circuit( V): | AC 380( 400, 660) |
---|---|---|---|
Busbar: | 3-Phase And 4-Wire | Form: | All- Packaged Type |
Highlight: | high voltage gas insulated switchgear,gas insulated switchgear |
Indoor Gas Insulated Switchgear Metal Clad Power Equipment
Product
Overview
XGN49-40.5(Z)[DXG-40.5(Z)] Indoor Gas Insulating Metal-clad Switchgear (hereinafter referred to as “C-GIS”) is a high technology product which is researched, developed and manufactured on the basis of technology introduction of China Power Industry Federation Longyuan Power Research Institute. It meets GB/T11022 namely “Technical Requirements of HV Switchgear and Controller” and GB3906 namely “3-35KV AC Metal-clad Switchgear”. It has the characteristics of high reliability, free from maintenance and small cover area. Main technical parameters have arrived to international advanced level.
Features
a. Adopt module design.
b. Metal clad enclosure is made of 4~6mm high quality steel plate and welded by machine hand. The enclosure is sealed well and ensures no gas leakage for 30 years, The enclosure can not be distorted in high altitude.
c. Incoming and outgoing cables are connected with the special cable head and inner cone type insulator.
d. Epoxy resin is adopted to pour busbar through type CT.
e. The secondary winding is fitted with intelligent control/protection unit containing control, protection, measurement and signal function, or traditional relay protection.
f. Gas isolators are adopted to connect main busbar between cubicles, which can ensure electrical insulation and gas tightness of busbar room.
Parameters
Name | Unit | Parameters | |
Rated Voltage | kV | 40.5 | |
Rated Current | A | 5~1250 | |
Rated Frequency | Hz | 50 | |
Rated Power Frequency Withstand Voltage (1min) | Between Phases, Phase to Earth | kV | Rated Power Frequency Withstand Voltage (1 min) |
To open gap | |||
Rated Lightning Impulse Withstand Voltage | Between Phases, Phase to Earth | kV | Rated Lightning Impulse Withstand Voltage |
To open gap | |||
Secondary Circuit Power Frequency Withstand Voltage (1min) | V | 2000 | |
Rated Short-circuit Breaking Current | kA | 25 | |
Rated Short-circuit Making Current | kA | 63 | |
Rated Short-time Withstand Current | kA | 25 | |
Rated Peak Withstand Current | kA | 63 | |
Rated Short-circuit Duration | s | 4 | |
Enclosure Protection Class (Air Inflation Shell/LV Cubicle) | IP67/IP4X | ||
Main Circuit Resistance Each Phase | μΩ | ≤250 | |
Rated Operating Pressure of SF6 Gas (Gage pressure for 20℃ ) | Mpa | 0.05 | |
Minimum Operating Pressure of SF6 Gas (Gage pressure for 20℃ ) | Mpa | 0.02 | |
SF6 Gas Annual Gas Leakage Rate | % | ≤1 | |
Auxiliary Circuit Rated Operating Voltage | V | DC110/220 | |
Enclosure Dimension (Width*Depth*Height) | mm | (600~1200)*1400*2500 |