Product Details:
Payment & Shipping Terms:
|
Rated Insulation Voltage: | AC690V/AC1000V | Type: | Distribution Metering Box |
---|---|---|---|
Form: | Partly-welded Type | Application Range: | Power Plants |
Enclosure Protection Grade: | Ip30/IP40/IP42 | Altitude: | Less Than 2000m At Site |
High Light: | low voltage metal clad switchgear,industrial electrical switchgear |
GCS/GCK Low Voltage Equipment Series Low Voltage Switchgear
General
ü It is widely applicable for low-voltage distribution system in power plants, substations, petroleum, chemical industries, factories and mining enterprises, high-rise buildings, etc.
ü It can be used as power transformation, distribution and control for power, lighting and heating.
ü GCS low voltage distribution cabinets have all realized domestication, and have reliable performance and moderate price, thus they’re cost-effective. The product is applicable in power grid of 5000A and below.
ü It is the power center and the main distribution device; it is the motor control center; it is a power distribution device.
ü The product meets the requirements of the national standard IEC61439-2,GB-7251-22.
A modular system
>> Standardized components.
>> Fast manufacturing.
>> Easy modifications.
Functional design
1) Rationalized dimensions and layout inside the switchboard.
2) Reduced footprint.
3) Easy power and auxiliary connections .
4) Easy installation upgrading at a controlled cost.
5) An intelligent system, ready to integrate devices containing advanced protection and communication
functions for electrical distribution and motor control.
Standard colors
>> RAL 9002 (grayish white) / RAL 7016 (graphite grey).
Specifications
Rated voltage of main circuit( V) | AC 380( 400, 660) | |
Rated voltage of auxiliary circuit( V) | AC 220 380( 400) DC 110, 220 |
|
Rated frequency( Hz) | 50( 60) | |
Rated insulation voltage( V) | 660( 1000) | |
Rated current ( A) | Horizontal busbar | < =4000 |
Vertical busbar | 1000 | |
Rated short time withstand current of busbar( kA/1s) | 50, 80 | |
Rated peak withstand current of busbar( kA/0.1s) | 105, 176 | |
Power frequency testing voltage (V/1min) | Main circuit | 2500 |
Auxiliary circuit | 1760 | |
Busbar | 3-phase and 4-wire | A. B. C. PEN |
3-phase and 5-wire | A. B. C. PE. N | |
Protection degree | IP3L0. IP4L0 | |
Dimensions | 2200x (600 800 1000)x600(800 1000) |