Product Details:
Payment & Shipping Terms:
|
Rated Operating Current: | 630A~100 | Breaking Capacity: | 15KA |
---|---|---|---|
Shell Material: | C-type Steel Plate | Shell Protection Grade: | IP30 |
Altitude: | Up To 2, 000m Above Sea Level | Busbar: | 3-Phase And 4-Wire |
Rated Voltage Of Main Circuit( V): | AC 380( 400, 660) | ||
High Light: | low voltage metal clad switchgear,industrial electrical switchgear |
Low Voltage Electrical Withdrawable Switchgear / Safety Electrical Switchgear
Description
The GGD AC low-voltage distribution cabinet is one new low-volt distribution cabinet elaborately designed in the light of safety, economical, reasonable and reliable principle for meeting the higher demand of energy-source ministry and majority of electrical customers,which Rated Voltage 380V, rated operating current being 630A or lower in power plant, transformer substation, mining enterprise etc, .
This productthnis mainly used for power transforming, distributing and controlling of power equipment, lighting and distribution equipment owns many advantages as high breaking capacity, well dynamic, thermal stability, flexible electric plan,upgraded product for low-volt completes set switch equipment.
The GGD conforms with techinique demand of IEC61439-2 and GB7251.12 etc.
Technical specification of MNS switchgear
Normal service conditions of switchgear as follows:
Ambient temperature: | |
Maximum | +40ºC |
Maximum 24 hour average | +35ºC |
Minimum (according to minus 15 indoor classes) | -5ºC |
Ambient humidity: | |
Daily average relative humidity | Less than 95% |
Monthly average relative humidity | Less than 90% |
Height above sea level at site | Less than 2000m |
Earthquake intensity | Less than 8 degree |
This product should not be used under conditions of fire, explosion, earthquake and chemical corrosion environments.
Item | Unit | Technical Data |
Rated voltage | V | 380/400 |
Rated insulation voltage | V | 660/1000 |
Rated frequency | HZ | 50/60 |
Rated main bus bar max. current | A | 630A 3150A |
Rated short time withstand current of main bus bar (1s) | KA | 50/80 |
Rated short time peak withstand current of main bus bar | KA | 105 |
Rated distribution bus bar current | A | 1000 |
Degree of protection | IP30,IP40 |
Contact Person: Ms. Lian Huanhuan
Tel: +86-13858385873
Fax: 86-574-87911400