XGN49Series lndoor Gas lnsulatlon MetaI-clad Switchgear(hereinafter called C-GlS)is a high quality product which the China power industry federation sole recommends technology from Korea Rijin electrical equipment industry corporation and it meets Chinese standards of GB/T11022-1999 and GB3906-2006C-GlS,has the characteristics of high reliability,free from maintenance and small cover area.
Parameters Table
Item | Unit | Parameter | |
Rated voltage | kV | 40.5 | |
Rated current | A | 5~2000 | |
Rated frequency | Hz | 50 | |
Rated power frequency withstand voltage (1min) | Phase to phase, Phase to earth | kV | 95 |
Insulation Distance | 110 | ||
Rated Lightning impulse withstand voltage | Phase to phase, Phase to earth | kV | 185 |
Insulation Distance | 215 | ||
1min power frequency withstand voltage of Auxiliary control circuit | V | 2000 | |
Rated short-circuit breaking current (effective value) | kA | 20 25 31.5 | |
Rated short-circuit making current(peak time) | kA | 50 63 80 | |
Rated short time withstand current | kA | 20 25 31.5 | |
Rated peak withstand current | kA | 50 63 80 | |
Rated short-circuit keeping time | s | 4 | |
Degrees of protection | IP67/IP4X | ||
Every phase main return circuit resistance | μΩ | ≤250 | |
Rated SF6 gas pressure (20°C) | Mpa | 0.05 | |
Min SF6 gas pressure (20°C) | Mpa | 0.02 | |
Annual SF6 gas loss rate | % | ≤1 | |
Rated voltage of auxiliary control circuit | V | DC110/220,AC220 | |