Product Details:
Payment & Shipping Terms:
|
Phase: | Three | Core: | Core-type Transformer |
---|---|---|---|
Cooling Method: | Oil-immersed Type Transformer | Mechanical Endurance: | 2000 |
Rated Current: | 315A/630A | Voltage: | 12KV |
High Light: | oil immersed distribution transformer,packaged transformer substation |
Wind transformer substation step up Oil immersed Type Transformer
Summarize
ZGS-Z.F-/11 series wind power combined transformer is a special power equipment integrating step-up transformer, HV current limited fuse, load switch, LV switch and related auxiliary equipments. It transforms the 0.69kV voltage produced by wind power motor into 35kV,and output the electricity through 35KV cable circuit, which is the ideal equipment in wind power complete set equipment.
Normal Ambient Conditions for Service
Altitude shall be within 2000m
Ambient temperature range shall be : -40ºC~+40ºC
Outdoor wind speed shall not exceeds 35m/s
Relative humidity: daily average value shall not exceed 95%, monthly average value 90%
Installation site: indoor
Service environment: installed in sites with no fire or explosion danger, serious fifth, chemical corrosion and fierce vibration.
When transcend the above normal ambient conditions for service, users can negotiate with us to solve.
Product technical parameter
S/N |
Name | Unit | Parameter | ||
1 | Rated voltage | KV | 12 | ||
2 | Rated current | A | 315 | 630 | |
3 | Rated frequency | Hz | 50 | ||
4 | Rated short-circuit withstand current | kA/2s | 12.5 | 20 | |
5 | Rated peak withstand current | kA | 31.5 | 50 | |
6 | Mechanical endurance | times | 2000 | ||
7 | 1 min power withstand voltage (phase-to-phase, phase-to-earth) | kV | 42 | ||
8 | Lightning impulse level (phase-to-phase, phase-to-earth) | KV | 75 | ||
Rated voltage | Fuse rated current A | Rated Max. breaking current kA | Remark |
15.5 | 63, 80,100,125,150 | 50 | off line |
Rated voltage | Continuous operating voltage | DC reference voltage (1mA) | Nominal discharging current | Nominal discharging current residual | 2ms square-wave current withstand value |
17kV | 13.6kV | ≥24kV | 5kA(peak value) | ≤45kV (peak value) | ≥250A(peak value) |
Parameter of 11kV oil immersed load switch
Table 1
Parameter of 11kV fuse
Table 2
Parameter of lightning arrester
Table 3
Main technical parameter of transformer
Voltage combination
Rated voltage of HV side: 12kV
Rated voltage of LV side: 0.27kV, 0.3kV, 0.315kV, 0.4kV
HV tapping range+5% or + 2x2.5%
Connecting symbol: Dyn11 or Yyn0
Condensation controller and other auxiliary equipment can be added in the body as per clients' requests.
Insulation class: A class
No. of phases: three
Note: As per different requirement from client, the capacity of transformer can be customized.