                     Product Details: 
						                        
 Payment & Shipping Terms: 
							
  | 
                            
| Installation: | Outdoor High-voltage | Series: | Single-Stage | 
|---|---|---|---|
| Voltage Rating: | 330kV | Current Rating: | Up To 4000A | 
| Highlight: | isolator disconnector,hv disconnect switch | 
			    	||
| S/N | Item | Unit | Parameter | ||||
| 1 | Rated voltage | kV | 72.5 | 145 | 252 | 363 | 420 | 
| 2 | Rated insulation level | ||||||
| 3 | Rated power frequency withstand voltage (1 min) | ||||||
| 4 | To earth | kV | 160 | 275 | 460 | 210 | 520 | 
| 5 | Across open breaks | kV | 200 | 275+85 | 460+145 | 210+210 | 610 | 
| 6 | Rated lightning impulse withstand voltage | ||||||
| 7 | To earth | kV | 350 | 650 | 1050 | 1175 | 1425 | 
| 8 | Across open breaks | kV | 410 | 650+120 | 1050+200 | 1175+295 | 1425+240 | 
| 9 | Rated switch impulse withstand voltage (peak) | ||||||
| 10 | between phase/ to earth | kV | -- | -- | -- | 1425/950 | 1574/1050 | 
| 11 | Across open breaks | kV | -- | -- | -- | 850+295 | 900+345 | 
| 12 | Rated frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 
| 13 | Rated current | A | 1250 2000 2500 3150 4000  | 1250/2000 | 2000 2500 3150 4000 5000  | 31,505,000 | 3150 | 
| 14 | Rated short-time withstand current | kA | 40 50  | 31.5/40 | 50/63 | 160 | 160 | 
| 15 | Rated peak withstand current | kA | 100 125  | 80/100 | 125/160 | 63 | 63 | 
| 16 | Rated duration of short circuit | s | 4 | 4 | 3 | 3 | 2 | 
| 17 | Rated terminal mechanical load | ||||||
| 18 | Horizontal -logntitudinal | N | 750/1000 | 1250 | 1500 | 2500 | 2000 | 
| 19 | Horizontal- vertical | N | 500/750 | 750 | 1000 | 2000 | 660 | 
| 20 | Vertical force | N | 750 | 1000 | 1250 | 1500 | 1500 | 
| 21 | Isolating switch bus capacity of switching currents and opening/ closing  | 100V, 1600A, 100 times  | 100V, 1600A, 100 times  | 300V, 1600A, 100 times  | 450V, 3200A, 3times 400V, 1600A, 100 times  | 300V, 1600A, 100 times  | |
| 22 | Grounding switch induction current open/ closing capacity | ||||||
| 23 | Electromagnetic induction-typ current (current/ voltage) | A/kV | 100/4 (80/2) | 100/6 (80/2) | 160/15 (80/3) | 1250/35 (160/10) | 160/10 (80/2) | 
| 24 | electrostatic induction current (current/ voltage) | A/kV | 2/6 | 5/6 (2/6) | 10/15 (3/12) | 50/50 (18/17) | 18/20 (1.25/5) | 
| 25 | Times of opening and closing | times | 10 | 10 | 10 | 10 | 10 | 
| 26 | isolating switch small current open/ closing capacity | ||||||
| 27 | capacitive current | A | -- | 1 | 1 | 1 | 1 | 
| 28 | Inductive current | A | -- | 0.5 | 0.5 | 0.5 | 0.5 | 
| 29 | RIV radio interference voltage | uV | <500 | <500 | <500 | <500 | <500 | 
| 30 | Creepage distance | mm | >1813 2248  | >3625 4495  | >6300 7812  | >9450 | >10500 | 
| 31 | Mechnical endurance | times | 5000 | 5000 | 1000 | 5000 | 10000 | 
| 32 | Applicable altitudes | <2000 | <2000 | <2000 | <3000 | <1000 | |
| 33 | Motor operating mechanism | ||||||
| 34 | Model | CJ2 | CJ2 | SRCJ2 | SRCJ2 | SRCJ2 | |
| 35 | Motor voltage | V | AC 380 DC220  | AC 380 DC220  | AC 380 DC220  | AC 380 DC220  | AC 380 DC220  | 
| 36 | Control circuit's voltage | V | AC 220 DC220 DC110  | AC 220 DC220 DC110  | AC 220 DC220 DC110  | AC 220 DC220 DC110  | AC 220 DC220 DC110  | 
| 37 | Opening time and closing time | s | 7+1 | 7+1 | 16+1 | 16+1 | 16+1 | 
| 38 | Output shaft rotation | 180 | 180 | 180 | 180 | 180 | |
| 39 | Manual operating mechanism | ||||||
| 40 | Model | CS11 | CS11 | SRCS | SRCS | SRCS | |
| 41 | control circuit voltage | V | AC 220 | AC 220 | AC 220 | AC 220 | AC 220 | 
 
 
 ![]()