Product Details:
Payment & Shipping Terms:
|
| Voltage: | 12KV/400v | Capacity: | 30~2000 |
|---|---|---|---|
| Breaking Current Of Fuse: | 31.5/40 | Rated Current Of Main Circuit: | 100-4000A |
| Highlight: | oil immersed distribution transformer,packaged transformer substation |
||
| Items | Unit | Parameters | |
| High Voltage Part | Rated voltage | kV | 12 |
| Rated frequency | Hz | 50 | |
| Rated current of main busbar | A | 630 | |
| 1mm power frequency withstand voltage (to earth and between phases/disconnecting fracture) | kV | 42/48 | |
| Lightning impulse withstand voltage (to earth and between phases/disconnecting fracture) | kV | 75/85 | |
| Rated short time withstand current | kA/s | 25/2 | |
| Rated peak withstand current | kA | 63 | |
| Rated short time making current | kA | 50 | |
| Rated transfer current | A | 1500 | |
| Breaking current of fuse | kA | 31.5 40 | |
| Low Voltage Part | Rated voltage | V | 400 |
| Rated current of main circuit | A | 100-4000 | |
| Rated limiting short circuit breaking ability | kA | 80 | |
| Rated operating short circuit breaking ability | kA | 50 (65) | |
| Rated short time withstand current | kA/1s | 50 (65) | |
| Branch current,compensating capacity | According to requirements of users | ||
| Transformer | Rated capacity | kVA | 30-2000 |
| Impedance voltage | % | 4 4.5 | |
| Tapping range | % | ±2×2.5 ±5 | |
| Connection symbol | Y, yn0 D, yn11 | ||
| Case | Protection level of enclosure | IP23 | |
| Sound level | dB | ≤50 | |
Contact Person: Ms. Lian Huanhuan
Tel: +86-13858385873
Fax: 86-574-87911400