145kV Tested High Voltage AC Circuit Breaker SF6 Type With 3 Pole
Overview
LW36-145/T3150-40 HV AC SF6 circuit breaker is an outdoor product.It can also be used as a connection circuit breaker.
1. Altitudes : ≤ 2000m (product designs for 3000m are available)
2. Environment temperautere: -30ºC~+40ºC
3. Pollution grade: Class iV
Parameters
Table 1
No. | Items | Unit | Parameters | |
1 | System nominal voltage | kV | 145 | |
2 | Rated voltage | kV | 132 | |
3 | Rated frequency | Hz | 50 | |
4 | Rated current | A | 3150 | |
5 | Rated short-circuit breaking current | kA | 31.5 | 40 |
6 | Rated short-circuit making current | kA | 80 | 100 |
7 | Rated short time withstand current/time | kA/s | 31.5/4 | 40/3 |
8 | Rated peak withstand current | kA | 80 | 100 |
9 | First-pole-to-clear factor | 1.5 | ||
10 | Lightning impulse withstand voltage | kV | 650 | |
11 | 1min power frequency withstand voltage | kV | 275 | |
12 | Creepage distance fracture/to earth | cm/kV | 250/250 | |
13 | Rated operation order | O-0.3s-CO -180s-CO |
||
14 | Making time | ms | ≤110 | |
15 | Breaking time | ms | ≤65 | |
16 | Closing-opening time | ms | ≤100 | |
17 | Closing non-simultaneity | ms | ≤5 | |
18 | Opening non-simultaneity | ms | ≤3 | |
19 | Fracture no of per pole | piece | 1 | |
20 | Mechanical endurance | time | 6000 | |
21 | SF6 gas pressure Rated value (20ºC) Alarm value The lowest function pressure |
MPa MPa MPa |
0.55 0.50 0.45 |
0.60 0.55 0.50 |
22 | SF6 moisture content | ppm(V/V) | ≤150 | |
23 | SF6 yearly air leakage percentage | ≤1% | ||
24 | Per set circuit-breaker SF6 gas charging weight | kg | 9 | 11 |
25 | Gross weight of per set circuit-breaker | kg | 2200 | |
26 | Sub-static pull on wiring longitudinal terminal of circuit-breaker horizontal vertical |
N N N |
1250 750 1000 |
|
27 | Voltage of auxiliary circuit | V | AC220 | |
28 | Opening-closing coil rated voltage rated current |
V A |
DC220 or DC110 1.29 |
|
29 | Energy Storage motor rated voltage rated power |
V W |
AC220 or DC 220 700 |
|
30 | Energy storage time | s | ≤15 | |
31 | Heater voltage power |
V W |
AC220 100 |
|
32 | Standards | GB1984 |
3.2 Mechanical parameters of circuit breaker
Table 2
No. | Name | Unit | Parameters |
1 | Contact travel of moving-contact | mm | 38~42 |
2 | Main drive lever travel of mechanism | mm | 113~118 |
3 | Distance between opening movable and static contact | mm | 75~80 |