Rated Voltage: | 40.5 | Rated Current: | 630 |
---|---|---|---|
Altitude: | <1000m | Environmental Temperature: | -25℃~+40℃ |
Highlight: | three phase surge arrester,electrical surge arrester |
S/N |
Name |
Unit |
Parameter |
|||||
1 |
rated voltage |
kV |
40.5 |
|||||
2 |
rated frequency |
Hz |
50 |
|||||
3 |
rated current |
A |
630 |
|||||
4 |
rated current of fuse |
100 |
||||||
5 |
rated short time withstand current |
kA |
12.5 |
|||||
6 |
rated short circuit duration |
s |
4 |
|||||
7 |
rated short circuit making current |
kA |
31.5 |
|||||
8 |
Rated peak withstand current |
|
31.5 |
|||||
9 |
Rated load breaking current |
A |
630 |
|||||
10 |
Rated jump (connect) breaking current (For 100A Fuse) |
2000 |
||||||
11 |
Earthing switch making current |
kA |
31.5 |
|||||
12 |
FT16-40.5FT16-40.5 Resistance of main circuit |
uW |
180 |
|||||
13 |
FT16-40.5RFT16-40.5R Resistance of main circuit |
400 |
||||||
14 |
Opening time |
ms |
95+20 |
|||||
15 |
Rated breaking current of fuse |
kA |
31.5 |
|||||
16 |
Rated insulation level |
1minpower frequency withstand voltage (effective value) |
Phase to phase, Phase to earth |
kV |
95 |
|||
Distance |
115 |
|||||||
Lightning impulse withstand voltage (peak) |
Phase to phase, Phase to earth |
185 |
||||||
Distance |
215 |
|||||||
17 |
1min power frequency withstand voltage of secondary circuit |
2 |
||||||
18 |
Protection level |
HXGT16 |
|
IP2X |
||||
DFT16 |
|
IP33 |
||||||
19 |
Center distance of three phases |
|
420±3 |
|||||
20 |
Dimensions |
HXGT16 |
Width |
mm |
1400,1600,2100 |
|||
Depth |
1600 |
|||||||
Height |
2200 |
|||||||
DFT16 |
Width |
1800 |
||||||
Depth |
2300 |
|||||||
Height |
1900 |
|||||||
21 |
Mechanical life of load switch |
Load isolating |
times |
2000 |
||||
Earthing |
2000 |